CVEvulnerability
CVE-2011-20002
8.3 HIGH
Official page ↗
- Status
- Deferred
- Published
- 2025-10-14
- Last modified
- 2026-06-16
- Assigner
- [email protected]
- CVSS 4.0 ([email protected])
- 8.3 HIGH — CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
- CVSS 3.1 ([email protected])
- 7.4 HIGH — CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:H
- Weaknesses
- CWE-294
Description
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
Related
Weakness · CWE (1)
- CWE-294 Authentication Bypass by Capture-replay weakness
References
- https://cert-portal.siemens.com/productcert/html/ssa-625789.html cert-portal.siemens.com