CVEvulnerability

CVE-2016-4785

5.3 MEDIUM Published 2016-05-31 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2016-05-31
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.0 ([email protected])
5.3 MEDIUM — CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
CVSS 2.0 ([email protected])
5.0 MEDIUM — AV:N/AC:L/Au:N/C:P/I:N/A:N
Weaknesses
CWE-200

Description

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.

Affected configurations

• siemens siprotec firmware 4.26 • siemens siprotec firmware

Related

Weakness · CWE (1)

  • CWE-200 Exposure of Sensitive Information to an Unauthorized Actor weakness

References