CVEvulnerability
CVE-2017-6028
9.8 CRITICAL
Official page ↗
- Status
- Modified
- Published
- 2017-06-30
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- CVSS 2.0 ([email protected])
- 5.0 MEDIUM — AV:N/AC:L/Au:N/C:P/I:N/A:N
- Weaknesses
- CWE-522
Description
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
Affected configurations
• schneider-electric modicon m241 firmware (<= 4.0.3.20)
• schneider-electric modicon m251 firmware (<= 4.0.3.20)
Related
Weakness · CWE (1)
- CWE-522 Insufficiently Protected Credentials weakness
References
- http://www.securityfocus.com/bid/97254 Third Party Advisory, VDB Entry
- https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 Third Party Advisory, US Government Resource
- http://www.securityfocus.com/bid/97254 Third Party Advisory, VDB Entry
- https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 Third Party Advisory, US Government Resource