CVEvulnerability
CVE-2018-7522
6.7 MEDIUM
Official page ↗
- Status
- Modified
- Published
- 2018-05-04
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.0 ([email protected])
- 6.7 MEDIUM — CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
- CVSS 2.0 ([email protected])
- 7.2 HIGH — AV:L/AC:L/Au:N/C:C/I:C/A:C
- Weaknesses
- CWE-119
Description
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states.
Affected configurations
• schneider-electric triconex tricon mp 3008 firmware (>= 10.0 <= 10.0-10.4)
Related
Weakness · CWE (1)
- CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer weakness
References
- http://www.securityfocus.com/bid/103947 Third Party Advisory, VDB Entry
- https://ics-cert.us-cert.gov/advisories/ICSA-18-107-02 Third Party Advisory, US Government Resource
- https://www.schneider-electric.com/en/download/document/SEVD-2017-347-01/ Vendor Advisory
- http://www.securityfocus.com/bid/103947 Third Party Advisory, VDB Entry
- https://ics-cert.us-cert.gov/advisories/ICSA-18-107-02 Third Party Advisory, US Government Resource
- https://www.schneider-electric.com/en/download/document/SEVD-2017-347-01/ Vendor Advisory