CVEvulnerability

CVE-2019-10916

8.8 HIGH Published 2019-05-14 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2019-05-14
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
8.8 HIGH — CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
CVSS 2.0 ([email protected])
9.0 HIGH — AV:N/AC:L/Au:S/C:C/I:C/A:C
Weaknesses
CWE-89

Description

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file. The vulnerability does impact the confidentiality, integrity, and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Affected configurations

• siemens simatic pcs 7 (<= 8.0) • siemens simatic pcs 7 8.1 • siemens simatic pcs 7 8.2 • siemens simatic pcs 7 9.0 • siemens simatic wincc (<= 7.2) • siemens simatic wincc 7.3 • siemens simatic wincc 7.4 • siemens simatic wincc 7.5 • siemens simatic wincc \(tia portal\) 13.0 • siemens simatic wincc \(tia portal\) 14.0 • siemens simatic wincc \(tia portal\) 15.0 • siemens simatic wincc runtime professional

Related

Weakness · CWE (1)

  • CWE-89 Improper Neutralization of Special Elements used in an SQL Command weakness

References