CVEvulnerability

CVE-2019-18336

7.5 HIGH Published 2020-03-10 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2020-03-10
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
7.5 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CVSS 3.1 (134c704f-9b21-4f2e-91b3-4a467353bcc0)
7.5 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CVSS 2.0 ([email protected])
7.8 HIGH — AV:N/AC:L/Au:N/C:N/I:N/A:C
Weaknesses
CWE-400

Description

A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.

Affected configurations

• siemens simatic s7-300 cpu firmware (< 3.3.17) • siemens simatic s7-300 cpu 312 ifm firmware (< 3.3.17) • siemens simatic s7-300 cpu 313 firmware (< 3.3.17) • siemens simatic s7-300 cpu 314 firmware (< 3.3.17) • siemens simatic s7-300 cpu 314 ifm firmware (< 3.3.17) • siemens simatic s7-300 cpu 315 firmware (< 3.3.17) • siemens simatic s7-300 cpu 315-2 dp firmware (< 3.3.17) • siemens simatic s7-300 cpu 316-2 dp firmware (< 3.3.17) • siemens simatic s7-300 cpu 318-2 firmware (< 3.3.17) • siemens sinumerik 840d sl (< 4.8.6) • siemens sinumerik 840d sl (< 4.94) • siemens simatic tdc cp51m1 firmware (< 1.1.8) • siemens simatic tdc cpu555 firmware (< 1.1.1)

Related

Weakness · CWE (1)

  • CWE-400 Uncontrolled Resource Consumption weakness

References