CVEvulnerability
CVE-2020-10920
9.8 CRITICAL
Official page ↗
- Status
- Modified
- Published
- 2020-07-23
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- CVSS 3.0 ([email protected])
- 9.8 CRITICAL — CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- CVSS 2.0 ([email protected])
- 7.5 HIGH — AV:N/AC:L/Au:N/C:P/I:P/A:P
- Weaknesses
- CWE-306
Description
This vulnerability allows remote attackers to execute arbitrary code on affected installations of C-MORE HMI EA9 Firmware version 6.52 touch screen panels. Authentication is not required to exploit this vulnerability. The specific flaw exists within the control service, which listens on TCP port 9999 by default. The issue results from the lack of authentication prior to allowing alterations to the system configuration. An attacker can leverage this vulnerability to execute code in the context of the device. Was ZDI-CAN-10493.
Affected configurations
• automationdirect c-more hmi ea9 firmware 6.52
Related
Weakness · CWE (1)
- CWE-306 Missing Authentication for Critical Functionality weakness
References
- https://www.zerodayinitiative.com/advisories/ZDI-20-808/ Third Party Advisory, VDB Entry
- https://www.zerodayinitiative.com/advisories/ZDI-20-808/ Third Party Advisory, VDB Entry