CVEvulnerability

CVE-2020-15782

9.8 CRITICAL Published 2021-05-28 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2021-05-28
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS 3.1 (134c704f-9b21-4f2e-91b3-4a467353bcc0)
9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS 2.0 ([email protected])
7.5 HIGH — AV:N/AC:L/Au:N/C:P/I:P/A:P
Weaknesses
CWE-119

Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.

Affected configurations

• siemens simatic driver controller firmware (< 2.9.2) • siemens s7-1200 cpu firmware (< 4.5.0) • siemens s7-1500 cpu firmware (< 2.9.2) • siemens simatic s7-1500 software controller • siemens simatic s7-plcsim advanced (< 4.0) • siemens et 200sp open controller firmware

Related

Weakness · CWE (1)

  • CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer weakness

References