CVEvulnerability

CVE-2020-25178

8.8 HIGH Published 2022-03-18 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2022-03-18
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
7.5 HIGH — CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H
CVSS 3.1 ([email protected])
8.8 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
CVSS 2.0 ([email protected])
9.3 HIGH — AV:N/AC:M/Au:N/C:C/I:C/A:C
Weaknesses
CWE-319

Description

ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.

Affected configurations

• schneider-electric easergy t300 firmware (<= 2.7.1) • schneider-electric easergy c5 firmware (< 1.1.0) • schneider-electric micom c264 firmware (< d6.1) • schneider-electric pacis gtw firmware 5.1 • schneider-electric pacis gtw firmware 5.2 • schneider-electric pacis gtw firmware 6.1 • schneider-electric pacis gtw firmware 6.3 • schneider-electric saitel dp firmware (<= 11.06.21) • schneider-electric epas gtw firmware 6.4 • schneider-electric saitel dr firmware (<= 11.06.12) • schneider-electric scd2200 firmware (<= 10024) • rockwellautomation aadvance controller (<= 1.40) • rockwellautomation isagraf free runtime (<= 6.6.8) • rockwellautomation isagraf runtime (>= 5.0 < 6.0) • rockwellautomation micro810 firmware • rockwellautomation micro820 firmware • rockwellautomation micro830 firmware • rockwellautomation micro850 firmware • rockwellautomation micro870 firmware • xylem multismart firmware (< 3.2.0)

Related

Weakness · CWE (1)

  • CWE-319 Cleartext Transmission of Sensitive Information weakness

References