CVEvulnerability
CVE-2021-32978
7.5 HIGH
Official page ↗
- Status
- Modified
- Published
- 2022-04-04
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 7.5 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
- CVSS 3.1 ([email protected])
- 7.5 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
- CVSS 2.0 ([email protected])
- 5.0 MEDIUM — AV:N/AC:L/Au:N/C:P/I:N/A:N
- Weaknesses
- CWE-256, CWE-522
Description
The programming protocol allows for a previously entered password and lock state to be read by an attacker. If the previously entered password was successful, the attacker can then use the password to unlock Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00.
Affected configurations
• automationdirect c0-10dd1e-d firmware (< 3.00)
• automationdirect c0-10dd2e-d firmware (< 3.00)
• automationdirect c0-10dre-d firmware (< 3.00)
• automationdirect c0-10are-d firmware (< 3.00)
• automationdirect c0-11dd1e-d firmware (< 3.00)
• automationdirect c0-11dd2e-d firmware (< 3.00)
• automationdirect c0-11dre-d firmware (< 3.00)
• automationdirect c0-11are-d firmware (< 3.00)
• automationdirect c0-12dd1e-d firmware (< 3.00)
• automationdirect c0-12dd2e-d firmware (< 3.00)
• automationdirect c0-12dre-d firmware (< 3.00)
• automationdirect c0-12are-d firmware (< 3.00)
• automationdirect c0-12dd1e-1-d firmware (< 3.00)
• automationdirect c0-12dd2e-1-d firmware (< 3.00)
• automationdirect c0-12dre-1-d firmware (< 3.00)
• automationdirect c0-12are-1-d firmware (< 3.00)
• automationdirect c0-12dd1e-2-d firmware (< 3.00)
• automationdirect c0-12dd2e-2-d firmware (< 3.00)
• automationdirect c0-12dre-2-d firmware (< 3.00)
• automationdirect c0-12are-2-d firmware (< 3.00)
Related
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-21-166-02 Third Party Advisory, US Government Resource
- https://www.cisa.gov/uscert/ics/advisories/icsa-21-166-02 Third Party Advisory, US Government Resource