CVEvulnerability
CVE-2022-29952
9.1 CRITICAL
Official page ↗
- Status
- Modified
- Published
- 2022-07-26
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 9.1 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
- Weaknesses
- CWE-306
Description
Bently Nevada condition monitoring equipment through 2022-04-29 mishandles authentication. It utilizes the TDI command and data protocols (60005/TCP, 60007/TCP) for communications between the monitoring controller and System 1 and/or Bently Nevada Monitor Configuration (BNMC) software. These protocols provide configuration management and historical data related functionality. Neither protocol has any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality.
Affected configurations
• bakerhughes bently nevada 3701\/40 firmware (< 4.1)
• bakerhughes bently nevada 3701\/44 firmware (< 4.1)
• bakerhughes bently nevada 3701\/46 firmware (< 4.1)
• bakerhughes bently nevada 60m100 firmware
Related
Weakness · CWE (1)
- CWE-306 Missing Authentication for Critical Functionality weakness
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-188-02 Mitigation, Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/ Third Party Advisory
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-188-02 Mitigation, Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/ Third Party Advisory