CVEvulnerability

CVE-2022-30320

4.3 MEDIUM Published 2022-07-28 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2022-07-28
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
4.3 MEDIUM — CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
Weaknesses
CWE-327

Description

Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Affected configurations

• honeywell saia pg5 controls suite

Related

Weakness · CWE (1)

  • CWE-327 Use of a Broken or Risky Cryptographic Algorithm weakness

Referenced by CWE · observed example (2)

  • CWE-327 Use of a Broken or Risky Cryptographic Algorithm weakness
  • CWE-328 Use of Weak Hash weakness

References