CVEvulnerability
CVE-2022-31204
7.5 HIGH
Official page ↗
- Status
- Modified
- Published
- 2022-07-26
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 7.5 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
- Weaknesses
- CWE-319
Description
Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
Affected configurations
• omron sysmac cs1 firmware (< 4.1)
• omron sysmac cj2m firmware (< 2.1)
• omron sysmac cj2h firmware (< 1.5)
• omron sysmac cp1e firmware (< 1.30)
• omron sysmac cp1h firmware (< 1.30)
• omron sysmac cp1l firmware (< 1.10)
• omron cp1w-cif41 firmware
• omron cx-programmer (< 9.6)
Related
Weakness · CWE (1)
- CWE-319 Cleartext Transmission of Sensitive Information weakness
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02 Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/ Third Party Advisory
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02 Third Party Advisory, US Government Resource
- https://www.forescout.com/blog/ Third Party Advisory