CVEvulnerability

CVE-2023-28489

9.8 CRITICAL Published 2023-04-11 Modified 2026-06-17 Official page ↗
Status
Modified
Published
2023-04-11
Last modified
2026-06-17
Assigner
[email protected]
CVSS 3.1 ([email protected])
9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS 3.1 ([email protected])
9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Weaknesses
CWE-77

Description

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default. The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.

Affected configurations

• siemens cp-8031 firmware (< cpci85 v05) • siemens cp-8050 firmware (< cpci85 v05)

Related

Weakness · CWE (1)

  • CWE-77 Improper Neutralization of Special Elements used in a Command weakness