CVEvulnerability

CVE-2025-26389

10.0 CRITICAL Published 2025-05-13 Modified 2026-06-17 Official page ↗
Status
Analyzed
Published
2025-05-13
Last modified
2026-06-17
Assigner
[email protected]
CVSS 4.0 ([email protected])
10.0 CRITICAL — CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
CVSS 3.1 ([email protected])
10.0 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
CVSS 3.1 ([email protected])
9.8 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Weaknesses
CWE-78

Description

A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.

Affected configurations

• siemens ozw672 firmware (< 8.0) • siemens ozw772 firmware (< 8.0)

Related

Weakness · CWE (1)

  • CWE-78 Improper Neutralization of Special Elements used in an OS Command weakness

References