CVEvulnerability
CVE-2025-7693
9.3 CRITICAL
Official page ↗
- Status
- Deferred
- Published
- 2025-08-18
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 4.0 ([email protected])
- 9.3 CRITICAL — CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
- Weaknesses
- CWE-20
Description
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
Related
Weakness · CWE (1)
- CWE-20 Improper Input Validation weakness
References
- https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1736.html www.rockwellautomation.com