CVE-2026-3611
10.0 CRITICAL
Official page ↗
- Status
- Analyzed
- Published
- 2026-03-12
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 4.0 ([email protected])
- 10.0 CRITICAL — CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
- CVSS 3.1 ([email protected])
- 10.0 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
- CVSS 3.1 ([email protected])
- 10.0 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
- Weaknesses
- CWE-306
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Affected configurations
• honeywell iq4e firmware (< 3.30)
• honeywell iq412 firmware (< 3.30)
• honeywell iq422 firmware (< 3.30)
• honeywell iq4nc firmware (< 3.30)
• honeywell iq41x firmware (< 3.30)
Related
Weakness · CWE (1)
- CWE-306 Missing Authentication for Critical Functionality weakness
References
- https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json Issue Tracking
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03 Third Party Advisory, US Government Resource
- https://www.honeywell.com/us/en/contact Product