CVEvulnerability

CVE-2026-3611

10.0 CRITICAL Published 2026-03-12 Modified 2026-06-17 Official page ↗
Status
Analyzed
Published
2026-03-12
Last modified
2026-06-17
Assigner
[email protected]
CVSS 4.0 ([email protected])
10.0 CRITICAL — CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
CVSS 3.1 ([email protected])
10.0 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
CVSS 3.1 ([email protected])
10.0 CRITICAL — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
Weaknesses
CWE-306

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected configurations

• honeywell iq4e firmware (< 3.30) • honeywell iq412 firmware (< 3.30) • honeywell iq422 firmware (< 3.30) • honeywell iq4nc firmware (< 3.30) • honeywell iq41x firmware (< 3.30)

Related

Weakness · CWE (1)

  • CWE-306 Missing Authentication for Critical Functionality weakness