MITRE ATT&CKtechnique

T0835 Manipulate I/O Image

Published 2020-05-21 Modified 2026-10-13 Official page ↗
Domain
ics
Tactics
Inhibit Response Function
Platforms
Embedded
Version
1.1
Created
2020-05-21

Description

Adversaries may manipulate the I/O image of PLCs through various means to prevent them from functioning as expected. Methods of I/O image manipulation may include overriding the I/O table via direct memory manipulation or using the override function used for testing PLC programs. During the scan cycle, a PLC reads the status of all inputs and stores them in an image table. The image table is the PLCs internal storage location where values of inputs/outputs for one scan are stored while it executes the user program. After the PLC has solved the entire logic program, it updates the output image table. The contents of this output image table are written to the corresponding output points in I/O Modules. One of the unique characteristics of PLCs is their ability to override the status of a physical discrete input or to override the logic driving a physical output coil and force the output to a desired status.

Related

Tactic · MITRE ATT&CK (1)

  • TA0107 Inhibit Response Function tactic

Referenced by MITRE ATT&CK · mitigates (1)

  • M0816 Mitigation Limited or Not Effective mitigation

Referenced by MITRE ATT&CK · uses (2)

  • S0603 Stuxnet software (malware)
  • S1006 PLC-Blaster software (malware)