MITRE ATT&CKtechnique

T0858 Change Operating Mode

Published 2020-05-21 Modified 2026-10-13 Official page ↗
Domain
ics
Tactics
Execution, Evasion
Platforms
Embedded
Version
1.0
Created
2020-05-21

Description

Adversaries may change the operating mode of a controller to gain additional access to engineering functions such as Program Download. Programmable controllers typically have several modes of operation that control the state of the user program and control access to the controllers API. Operating modes can be physically selected using a key switch on the face of the controller but may also be selected with calls to the controllers API. Operating modes and the mechanisms by which they are selected often vary by vendor and product line. Some commonly implemented operating modes are described below: • Program - This mode must be enabled before changes can be made to a devices program. This allows program uploads and downloads between the device and an engineering workstation. Often the PLCs logic Is halted, and all outputs may be forced off. • Run - Execution of the devices program occurs in this mode. Input and output (values, points, tags, elements, etc.) are monitored and used according to the programs logic. Program Upload and Program Download are disabled while in this mode. • Remote - Allows for remote changes to a PLCs operation mode. • Stop - The PLC and program is stopped, while in this mode, outputs are forced off. • Reset - Conditions on the PLC are reset to their original states. Warm resets may retain some memory while cold resets will reset all I/O and data registers. • Test / Monitor mode - Similar to run mode, I/O is processed, although this mode allows for monitoring, force set, resets, and more generally tuning or debugging of the system. Often monitor mode may be used as a trial for initialization.

Related

Tactic · MITRE ATT&CK (2)

Referenced by MITRE ATT&CK · mitigates (7)

  • M0800 Authorization Enforcement mitigation
  • M0801 Access Management mitigation
  • M0802 Communication Authenticity mitigation
  • M0804 Human User Authentication mitigation
  • M0807 Network Allowlists mitigation
  • M0930 Network Segmentation mitigation
  • M0813 Software Process and Device Authentication mitigation

Referenced by MITRE ATT&CK · uses (3)

  • S1045 INCONTROLLER software (malware)
  • S1006 PLC-Blaster software (malware)
  • S1009 Triton software (malware)