CVEvulnerability
CVE-2022-40179
8.1 HIGH
Official page ↗
- Status
- Modified
- Published
- 2022-10-11
- Last modified
- 2026-06-17
- Assigner
- [email protected]
- CVSS 3.1 ([email protected])
- 8.1 HIGH — CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N
- Weaknesses
- CWE-352
Description
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). A Cross-Site Request Forgery exists in endpoints of the “Operation” web application that interpret and execute Axon language queries, due to the missing validation of anti-CSRF tokens or other origin checks. By convincing a victim to click on a malicious link or visit a specifically crafted webpage while logged-in to the device web application, a remote unauthenticated attacker can execute arbitrary Axon queries against the device.
Affected configurations
• siemens desigo pxm30-1 firmware (< 02.20.126.11-41)
• siemens desigo pxm30.e firmware (< 02.20.126.11-41)
• siemens desigo pxm40-1 firmware (< 02.20.126.11-41)
• siemens desigo pxm40.e firmware (< 02.20.126.11-41)
• siemens desigo pxm50-1 firmware (< 02.20.126.11-41)
• siemens desigo pxm50.e firmware (< 02.20.126.11-41)
• siemens pxg3.w100-1 firmware (< 02.20.126.11-37)
• siemens pxg3.w100-2 firmware (< 02.20.126.11-41)
• siemens pxg3.w200-1 firmware (< 02.20.126.11-37)
• siemens pxg3.w200-2 firmware (< 02.20.126.11-41)
Related
Weakness · CWE (1)
- CWE-352 Cross-Site Request Forgery weakness
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf Patch, Vendor Advisory
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf Patch, Vendor Advisory